HSA-275 M S (Surge Arrester) : TYPE 2+3, CLASS II+III

Hakel
HSA-275 M S

HSA-275 M S

  • Surge arresters type T2+T3 ensure the equipotential bonding and reduce switching, induced and residual overvoltage in LV power supply systems.
  • The products consist of varistors with big discharge ability. 
  • In 1+1 and 3+1 configurations they are additionaly combined with a gas discharge tube, which ensures zero leakage current through the PE conductor.
  • Installed at the boundaries of LPZ 1 – LPZ 3 into subsidiary switchboards and control panels.
  • If the product contains two PE (or PEN) terminals, it must not be used as a PE (PEN) bridge.
  • M indication specifies a type of construction with removable module.
  • S indication specifies a version with remote monitoring.
HSA-275 M S
Dimension drawing
HSA-275 M S
Internal wiring diagram
HSA-275 M S
Installation diagram
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T2, T3
System TN
Number of poles
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 275 V
Maximum discharge current (8/20) Imax 50 kA
Nominal discharge current for class II test (8/20) In 20 kA
Open circuit voltage of the combination wave generator UOC 6 kV
Voltage protection level at In Up < 1.25 kV
Voltage protection level at UOC Up < 0.85 kV
Temporary overvoltage test (TOV) for tT = 5 s UT 337 V
Temporary overvoltage test (TOV) for tT = 120 min UT 440 V
Response time tA < 25 ns
Maximal back-up fuse 160 A gL/gG
Residual current IPE ≤ 450 µA
Short-circuit current rating at maximum back-up fuse ISCCR 60 kArms
Lightning protection zone LPZ1, LPZ2, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Humidity range RH 5 ÷ 95 %
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-534:2016 (doesn't apply to „V“ connection) for T2 S 2.5 mm² (L, N)
6 mm² (PE, PEN)
Clamp fastening range (solid conductor) 1.5 ÷ 25 mm2
Clamp fastening range (stranded conductor) 1.5 ÷ 16 mm2
Tightening moment 3
Installation On DIN rail 35 mm
Modular width 1
Operating position Any
Product placement environment Internal
Signalling at the device Optic
Importance of local signaling OK – clear target
FAULT – red target
Remote signalling Yes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Modular design Yes
Article number of spare module 27 086
Lifetime > 100 000 h