HSA-275/3+0 M S (Surge Arrester) : TYPE 2+3, CLASS II+III , 3 Poles

Hakel
HSA-275-3-0 M S
  • HSA-275/3+0 M S (Hakel Surge Arrester) of the „G-Line“ range  is a surge arrester according to EN 61643-11:2012 (IEC 61643-11:2011) consisting of high energy varistors. Its parameters enable its use in complex circumstances. The device is to be installed on the interface of LPZ 1 – LPZ 2 and higher zones according to standard EN 62305:2011 (IEC 62305:2010), i.e. into subsidiary switchboards and control boxes.
  • Surge arresters type T2+T3 ensure the equipotential bonding and reduce switching, induced and residual overvoltage in LV power supply systems.
  • The products consist of varistors with big discharge ability.
  • Configurations 1+1 and 3+1 are additionally combined with a gas discharge tube which ensures zero leakage current through the PE conductor.
  • Installed at the boundaries of LPZ 1 – LPZ 3 into subsidiary switchboards and control panels.
  • If the product contains two PE (or PEN) terminals, it must not be used as a PE (PEN) bridge.
  • M indication specifies a type of construction with removable module.
  • S indication specifies a version with remote monitoring.
HSA-275-3-0 M S Diemension
Dimension drawing
HSA-275-3-0 M S Contact
Internal wiring diagram
HSA-275-3-0 M S single line
Installation diagram
Test class according to EN 61643-11:2012 (IEC 61643-11:2011)T2, T3
SystemTN-C
Number of poles3
Rated operating AC voltageUN230 V
Maximum continuous operating voltage ACUC275 V
Maximum discharge current (8/20)Imax50 kA
Nominal discharge current for class II test (8/20)In20 kA
Open circuit voltage of the combination wave generatorUOC6 kV
Total discharge current (8/20) L1+L2+L3->PENITotal150 kA
Voltage protection level at InUp< 1.25 kV
Voltage protection level at UOCUp< 0.85 kV
Temporary overvoltage test (TOV) for tT = 5 sUT337 V
Temporary overvoltage test (TOV) for tT = 120 minUT440 V
Response timetA< 25 ns
Maximal back-up fuse160 A gL/gG
Residual currentIPE≤ 200 µA
Short-circuit current rating at maximum back-up fuseISCCR60 kArms
Lightning protection zoneLPZ1, LPZ2, LPZ3
Housing materialPolyamid PA6, UL94 V-0
Degree of protectionIP20
Operating temperatureϑ- 40 ÷ 70 °C
Humidity rangeRH5 ÷ 95 %
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-534:2016 (doesn't apply to „V“ connection) for T2S2.5 mm² (L, N)
6 mm² (PE, PEN)
Clamp fastening range (solid conductor)1.5 ÷ 25 mm2
Clamp fastening range (stranded conductor)1.5 ÷ 16 mm2
Tightening moment3
InstallationOn DIN rail 35 mm
Modular width3
Operating positionAny
Product placement environmentInternal
Signalling at the deviceOptic
Importance of local signalingOK – clear target
FAULT – red target
Remote signallingYes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2)AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Modular designYes
Article number of spare module27 086
Lifetime> 100 000 h
Application standards
Protection against lightningIEC 62305:2010
Selection and erection of electrical equipment – Devices for protection against transient overvoltagesHD 60364-5-534:2016
Selection and application principles for SPDs connected to low-voltage power systemsCLC/TS 61643-12:2009
Designed according to standards
Requirements and test methods for SPDs connected to low-voltage power systemsIEC 61643-11:2011
Safety of Flammability of Plastic MaterialsUL 94